Abstract
Electrical power system is very complex and it requires very careful design of new equipment’s
which are needed to improve electric power utilization, enhancing power system stability, power
loss minimization and power transfer capability. The existing power transmission network of
Ethiopia consists of 45kV, 66kV, 132kV, 230kV and 400kV lines. This thesis mainly focused on
132kV transmission line of Eastern region of Ethiopia.
Transmission Line loss minimization and voltage profile improvement in the transmission line
are challenging problems. This thesis analyze the impact of using unified power flow controller
(UPFC) in the transmission line. The UPFC is the most versatile and complex power electronics
equipment’s that has emerged for control and optimization of power flow in electric power
transmission systems. It is a combination of series and parallel compensation and can therefore
provide active and reactive control to achieve maximum power transfer, system stability, and
voltage profile improvement and minimize transmission line loss.
Unified Power Flow Controller is designed for the transmission line to increase power transfer
capability, reduce power loss and improve voltage profile. The UPFC has been simulated using
DIgSILENT Power Factory Software. The simulation results showed that all the bus voltages are
within acceptable limit which is above 0.95p.u. After incorporating the UPFC the total active
power loss is reduced from 4.295MW to 1.908, from 2.387MW to 1.306MW and from 1.166MW
to 0.454MW for peak load condition, average load condition and minimum load condition
respectively. The total reactive power loss is reduced from 9.2MVAr to 3.3MVAr, from 6.1MVAr
to 2MVAr and from 4.6MVAr to 0.9MVAr for peak load condition, average load condition and
minimum load condition respectively.
Therefore, by incorporating the designed Unified Power Flow Controller voltage profiles in the
Eastern Region of Ethiopia is improved and transmission line loss is minimized.
Description
Keywords
Load Flow analysis, UPFC, FACTS, Power loss minimization, Voltage Profile improvement, DIgSILENT Power Factory